Benchmark Results

Though the systems are equipped with similar components, some notable observations can be made. Each benchmark was executed three times to verify the accuracy of our results. All ratios are calculated using the Dell R730 as baseline (=100%).

OLAP 95pct Response Time
(Lower is better)
Power
(Lower is better)
Throughput
(Higher is better)
Concurrency Facebook
Leopard
Intel
Decathlete v2
Facebook
Leopard
Intel
Decathlete v2
Facebook
Leopard
Intel
Decathlete v2
5 114% 111% 99% 99% 94% 117%
10 108% 105% 99% 98% 96% 109%
25 96% 94% 100% 101% 100% 116%
50 98% 56% 103% 110% 101% 112%
100 96% 49% 110% 149% 103% 119%
250 98% 67% 105% 144% 103% 120%
250 95% 67% 106% 144% 103% 120%
250 95% 67% 105% 143% 102% 120%
250 90% 62% 106% 143% 103% 121%

An interesting result: the Dell outperforms both Open Compute servers when it comes to energy efficiency. It is good to remember that the PSU used for the Facebook server is not optimal (it should get its power from a power shelf). Leopard is very close, and gets a slightly better performance mark, while Decathlete is a respectable 20% faster, but uses 40% more power in the process.

Next, we tested with our real-world Elasticsearch benchmark. Due to ES's internal queuing algorithm, the throughput and response time can vary wildly when it drops a 'heavy' request to allow it to pass many smaller ones, and we've seen the inverse happen as well. These tests were executed five times to confirm ensure the consistency of most results.

ElasticSearch 95pct Response Time
(Lower is better)
Power
(Lower is better)
Throughput
(Higher is better)
Concurrency Leopard Decathlete v2 Leopard Decathlete v2 Leopard Decathlete v2
5 115% 73% 107% 106% 96% 104%
10 88% 88% 75% 94% 101% 101%
25 74% 26% 90% 98% 118% 165%
50 96% 41% 95% 104% 100% 153%
100 97% 74% 98% 108% 107% 124%
200 103% 85% 97% 112% 108% 129%
200 96% 75% 100% 110% 108% 130%
200 89% 66% 95% 112% 110% 137%
200 96% 80% 95% 108% 113% 128%
250 92% 70% 97% 113% 101% 121%

Whereas the Dell and Leopard performed comparably in the OLAP test, ElasticSearch tests results are in favor of the Leopard. The throughput and response times are slightly better and Leopard uses slightly less power resulting in a tangibly better performance/watt with a sub optimal power supply. The Decathlete system gets the best scores on the board again, but this time the power usage increase is relatively modest: 8 to 13 percent.

Benchmark Configuration: Leopard Under Stress Visiting Facebook's Labs & Alternative OCP Standards
Comments Locked

26 Comments

View All Comments

  • Black Obsidian - Tuesday, April 28, 2015 - link

    I've always hoped for more in-depth coverage of the OpenCompute initiative, and this article is absolutely fantastic. It's great to see a company like Facebook innovating and contributing to the standard just as much as (if not more than) the traditional hardware OEMs.
  • ats - Tuesday, April 28, 2015 - link

    You missed the best part of the MS OCS v2 in your description: support for up to 8 M.2 x4 PCIe 3.0 drives!
  • nmm - Tuesday, April 28, 2015 - link

    I have always wondered why they bother with a bunch of little PSU's within each system or rack to convert AC power to DC. Wouldn't it make more sense to just provide DC power to the entire room/facility, then use less expensive hardware with no inverter to convert it to the needed voltages near each device? This type of configuration would get along better with battery backups as well, allowing systems to run much longer on battery by avoiding the double conversion between the battery and server.
  • extide - Tuesday, April 28, 2015 - link

    The problem with doing a datacenter wide power distribution is that at only 12v, to power hundreds of servers you would need to provide thousands of amps, and it is essentially impossible to do that efficiently. Basicaly the way FB is doing it, is the way to go -- you keep the 12v current to reasonable levels and only have to pass that high current a reasonable distance. Remember 6KW at 12v is already 500A !! And thats just for HALF of a rack.
  • tspacie - Tuesday, April 28, 2015 - link

    Telcos have done this at -48VDC for a while. I wonder did data center power consumption get too high to support this, or maybe just the big data centers don't have the same continuous up time requirements ?
    Anyway, love the article.
  • Notmyusualid - Wednesday, April 29, 2015 - link

    Indeed.

    In the submarine cable industry (your internet backbone), ALL our equipment is -48v DC. Even down to routers / switches (which are fitted with DC power modules, rather than your normal 100 - 250v AC units one expects to see).

    Only the management servers run from AC power (not my decision), and the converters that charge the DC plant.

    But 'extide' has a valid point - the lower voltage and higher currents require huge cabling. Once a electrical contractor dropped a piece of metal conduit from high over the copper 'bus bars' in the DC plant. Need I describe the fireworks that resulted?
  • toyotabedzrock - Wednesday, April 29, 2015 - link

    48 v allows 4 times the power at a given amperage.
    12vdc doesn't like to travel far and at the needed amperage would require too much expensive copper.

    I think a pair of square wave pulsed DC at higher voltage could allow them to just use a transformer and some capacitors for the power supply shelf. The pulses would have to be directly opposing each other.
  • Jaybus - Tuesday, April 28, 2015 - link

    That depends. The low voltage DC requires a high current, and so correspondingly high line loss. Line loss is proportional to the square of the current, so the 5V "rail" will have more than 4x the line loss of the 12V "rail", and the 3.3V rail will be high current and so high line loss. It is probably NOT more efficient than a modern PS. But what it does do is move the heat generating conversion process outside of the chassis, and more importantly, frees up considerable space inside the chassis.
  • Menno vl - Wednesday, April 29, 2015 - link

    There is already a lot of things going on in this direction. See http://www.emergealliance.org/
    and especially their 380V DC white paper.
    Going DC all the way, but at a higher voltage to keep the demand for cables reasonable. Switching 48VDC to 12VDC or whatever you need requires very similar technology as switching 380VDC to 12VDC. Of-course the safety hazards are different and it is similar when compared to mixing AC and DC which is a LOT of trouble.
  • Casper42 - Monday, May 4, 2015 - link

    Indeed, HP already makes 277VAC and 380VDC Power Supplies for both the Blades and Rackmounts.

    277VAC is apparently what you get when you split 480vAC 3phase into individual phases..